Bulk Cables  |  Multipair AF, safety & fire alarm cable, fixed installation, FRNC, E30-E90

balanced, solid wire conductors, halogen-free + flame-retardant E30-E90 accord. to DIN VDE 0815, AL/PT-foil with filler strand



  SOMMER CABLE - SC-LOGIC SAFETY MODFS02



installationELA

analogdigitalFRNChalogen-freeOFCE30E90



Fire...

for our safety cable SC-LOGIC SAFETY with continuous functions E30 - E90. This cable has become a standard cable for installation in public buildings and industrial facilities to transmit audio, control, and test signals. Due to the use of a special polymer it complies with the fire protection
requirements accord. to DIN VDE 4102 Part 12, E30 - E90.
Please note that this type of cable is not suitable for mobile application. Continued function depends on the installation technique. It is flame-retardant in compliance with DIN VDE 0482 Part 266-2, EN 50266-2, and IEC 60332-3, halogen-free in compliance with DIN VDE 0482 Parts 267-2 EN50267-2 and IEC 60754-2, impervious to smoke in compliance with DIN VDE 0482 Parts 268, EN 50268 and IEC 61034, fire resistance in connection with water at 650 °C: 15 minutes (BS8367; W).

THE ADVANTAGES:

  • Available in versions 1- to 20-pair
  • In compliance with the high fire protection requirement accord. to DIN VDE 4102 Part 12, E30 -E90
  • Simultaneous transmission of analog data and AES/EBU-data format


THE APPLICATION:

  • For fixed installation in buildings (airports, hospitals, traffic technology, industrial units, etc.)
  • Modulation cable for transmission of AES/EBU-Standards



TECHNICAL DATA:
ConstructionJ-H(ST)H..BD FE180/E90
Inner conductors2 x 2 x 0,8 mm
Jacket, diameterPolymer (DIN VDE 0207 HJ1/HD22.1.S4 EI5) 8,0 mm
AWG20
Conductor insulationCross link polymer, polyester, and fiber optic sleeve
ShieldingAL/PT-foil (total) with filler strand AWG26 (0.4 mm)
Shielding factor100 %
Temperature rangemin. -30 °C
Temperature rangemax. 70 °C
Fire load per m0,20 kWh
Weight per 1 m96 g
Jacket colorrot (RAL 3000)
Packagingper m

ELECTRICAL DATA:
Capac. cond./cond. per 1 m(800 Hz) 110 pF
Capac. cond./shield. per 1 m(800 Hz) 200 pF
Insulat. resistance per 1 km100 MOhm
Surge impedance(+/-10 %) 105 Ohm
Loop resistance per 1 km< 75 Ohm

ORDER DATA:
Order No.100-1173-02
Rec. priceon request



v2008-JUN-8